Permit Number: TC-COM-0224-00307
Parcel: 11015121B

Address:
5515 E GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0224-00307
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2024 Site Engineering APPROVED
11/22/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/04/2024 Commercial Electrical REQUIRES RESUBMIT November 4, 2024
1st Review

A23 Studios
Attn: Burak Bekat
711 E. 9th Street
Tucson, Arizona 85719

Re: MISTER CARWASH CRAYCROFT
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-0224-00307
Stantec Project Number: 185215066
Stantec File Number: TUC-24-135

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. To facilitate a shorter back-check time, we request that you please, only provide plans and calculation pages that have been revised, clouding any changes, along with a written response to each of the noted items indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 5,402 22 No No
Separate Permits: Signage, pre-engineered canopy and trellis.
Deferred Submittals: Pre-engineered wood trusses, pre-engineered canopies, pre-engineered awning and trellis.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, masonry, EFIS, and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Please clarify on the cover page that the sperate permit indicated for site utilities is specifically for private site sewer including any requirement for a backwater valve.

Sheet A1.0

1. Please revise comment 44 to clarify that the civil plans with the site sewer construction will be applied for separately.

STRUCTURAL COMMENTS

General

1. Please include the light pole footing design in the structural plan-set as this is addressed by the engineer of record.

Sheet S1.3

1. Please provide a site plan indicating the specific locations of the vacuum footings with a shade canopy and without a shade canopy. The architectural site plan does not show any canopies for the vacuums to differentiate the footing locations.

MECHANICAL COMMENTS

Sheet M1.0

1. The detail call-out for the drip pan of SAF-1 is incorrect. Please revise this to reflect the correct detail on Sheet M2.0.

2. Please revise the duct call-out for SAF-1 on the First Floor Plan from “EA UP” to “SA UP” as the ducting is supplying air from the supply air fan.

PLUMBING COMMENTS

Sheet P1.0

1. Please indicate on this sheet to clarify that the site utilities presented are diagrammatic only as the site sewer will be applied for under a separate permit. The original approved plan-set was red lined to reflect that the site sewer presented on this sheet was not approved because the site sewer is under a separate permit.

2. The cleanout indicated at the sewer line coming from Keynote 8 is not allowed. Cleanouts shall enable cleaning of drainage piping in the direction of drainage flow. [Ref. IPC 2018 Sec. 708.1.8]

Sheet P2.0

1. Please provide a label for the grade clean-out on the underground plan. [Ref. IPC 2018 Sec. 708.1.3]


ELECTRICAL COMMENTS

General

1. Please include the light pole footing design in the structural plan-set as this is addressed by the structural engineer of record.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
11/04/2024 Commercial Mechanical REQUIRES RESUBMIT November 4, 2024
1st Review

A23 Studios
Attn: Burak Bekat
711 E. 9th Street
Tucson, Arizona 85719

Re: MISTER CARWASH CRAYCROFT
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-0224-00307
Stantec Project Number: 185215066
Stantec File Number: TUC-24-135

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. To facilitate a shorter back-check time, we request that you please, only provide plans and calculation pages that have been revised, clouding any changes, along with a written response to each of the noted items indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 5,402 22 No No
Separate Permits: Signage, pre-engineered canopy and trellis.
Deferred Submittals: Pre-engineered wood trusses, pre-engineered canopies, pre-engineered awning and trellis.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, masonry, EFIS, and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Please clarify on the cover page that the sperate permit indicated for site utilities is specifically for private site sewer including any requirement for a backwater valve.

Sheet A1.0

1. Please revise comment 44 to clarify that the civil plans with the site sewer construction will be applied for separately.

STRUCTURAL COMMENTS

General

1. Please include the light pole footing design in the structural plan-set as this is addressed by the engineer of record.

Sheet S1.3

1. Please provide a site plan indicating the specific locations of the vacuum footings with a shade canopy and without a shade canopy. The architectural site plan does not show any canopies for the vacuums to differentiate the footing locations.

MECHANICAL COMMENTS

Sheet M1.0

1. The detail call-out for the drip pan of SAF-1 is incorrect. Please revise this to reflect the correct detail on Sheet M2.0.

2. Please revise the duct call-out for SAF-1 on the First Floor Plan from “EA UP” to “SA UP” as the ducting is supplying air from the supply air fan.

PLUMBING COMMENTS

Sheet P1.0

1. Please indicate on this sheet to clarify that the site utilities presented are diagrammatic only as the site sewer will be applied for under a separate permit. The original approved plan-set was red lined to reflect that the site sewer presented on this sheet was not approved because the site sewer is under a separate permit.

2. The cleanout indicated at the sewer line coming from Keynote 8 is not allowed. Cleanouts shall enable cleaning of drainage piping in the direction of drainage flow. [Ref. IPC 2018 Sec. 708.1.8]

Sheet P2.0

1. Please provide a label for the grade clean-out on the underground plan. [Ref. IPC 2018 Sec. 708.1.3]


ELECTRICAL COMMENTS

General

1. Please include the light pole footing design in the structural plan-set as this is addressed by the structural engineer of record.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
11/04/2024 Commercial Plumbing REQUIRES RESUBMIT November 4, 2024
1st Review

A23 Studios
Attn: Burak Bekat
711 E. 9th Street
Tucson, Arizona 85719

Re: MISTER CARWASH CRAYCROFT
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-0224-00307
Stantec Project Number: 185215066
Stantec File Number: TUC-24-135

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. To facilitate a shorter back-check time, we request that you please, only provide plans and calculation pages that have been revised, clouding any changes, along with a written response to each of the noted items indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 5,402 22 No No
Separate Permits: Signage, pre-engineered canopy and trellis.
Deferred Submittals: Pre-engineered wood trusses, pre-engineered canopies, pre-engineered awning and trellis.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, masonry, EFIS, and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Please clarify on the cover page that the sperate permit indicated for site utilities is specifically for private site sewer including any requirement for a backwater valve.

Sheet A1.0

1. Please revise comment 44 to clarify that the civil plans with the site sewer construction will be applied for separately.

STRUCTURAL COMMENTS

General

1. Please include the light pole footing design in the structural plan-set as this is addressed by the engineer of record.

Sheet S1.3

1. Please provide a site plan indicating the specific locations of the vacuum footings with a shade canopy and without a shade canopy. The architectural site plan does not show any canopies for the vacuums to differentiate the footing locations.

MECHANICAL COMMENTS

Sheet M1.0

1. The detail call-out for the drip pan of SAF-1 is incorrect. Please revise this to reflect the correct detail on Sheet M2.0.

2. Please revise the duct call-out for SAF-1 on the First Floor Plan from “EA UP” to “SA UP” as the ducting is supplying air from the supply air fan.

PLUMBING COMMENTS

Sheet P1.0

1. Please indicate on this sheet to clarify that the site utilities presented are diagrammatic only as the site sewer will be applied for under a separate permit. The original approved plan-set was red lined to reflect that the site sewer presented on this sheet was not approved because the site sewer is under a separate permit.

2. The cleanout indicated at the sewer line coming from Keynote 8 is not allowed. Cleanouts shall enable cleaning of drainage piping in the direction of drainage flow. [Ref. IPC 2018 Sec. 708.1.8]

Sheet P2.0

1. Please provide a label for the grade clean-out on the underground plan. [Ref. IPC 2018 Sec. 708.1.3]


ELECTRICAL COMMENTS

General

1. Please include the light pole footing design in the structural plan-set as this is addressed by the structural engineer of record.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
11/04/2024 Commercial Structural REQUIRES RESUBMIT November 4, 2024
1st Review

A23 Studios
Attn: Burak Bekat
711 E. 9th Street
Tucson, Arizona 85719

Re: MISTER CARWASH CRAYCROFT
NEW BUILDING (REVISIONS)

City of Tucson Permit Number: TC-COM-0224-00307
Stantec Project Number: 185215066
Stantec File Number: TUC-24-135

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. To facilitate a shorter back-check time, we request that you please, only provide plans and calculation pages that have been revised, clouding any changes, along with a written response to each of the noted items indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 5,402 22 No No
Separate Permits: Signage, pre-engineered canopy and trellis.
Deferred Submittals: Pre-engineered wood trusses, pre-engineered canopies, pre-engineered awning and trellis.
Special Inspections: Earthwork, concrete, epoxy and expansion anchors, masonry, EFIS, and outdoor lighting.

ARCHITECTURAL COMMENTS

General

1. Please clarify on the cover page that the sperate permit indicated for site utilities is specifically for private site sewer including any requirement for a backwater valve.

Sheet A1.0

1. Please revise comment 44 to clarify that the civil plans with the site sewer construction will be applied for separately.

STRUCTURAL COMMENTS

General

1. Please include the light pole footing design in the structural plan-set as this is addressed by the engineer of record.

Sheet S1.3

1. Please provide a site plan indicating the specific locations of the vacuum footings with a shade canopy and without a shade canopy. The architectural site plan does not show any canopies for the vacuums to differentiate the footing locations.

MECHANICAL COMMENTS

Sheet M1.0

1. The detail call-out for the drip pan of SAF-1 is incorrect. Please revise this to reflect the correct detail on Sheet M2.0.

2. Please revise the duct call-out for SAF-1 on the First Floor Plan from “EA UP” to “SA UP” as the ducting is supplying air from the supply air fan.

PLUMBING COMMENTS

Sheet P1.0

1. Please indicate on this sheet to clarify that the site utilities presented are diagrammatic only as the site sewer will be applied for under a separate permit. The original approved plan-set was red lined to reflect that the site sewer presented on this sheet was not approved because the site sewer is under a separate permit.

2. The cleanout indicated at the sewer line coming from Keynote 8 is not allowed. Cleanouts shall enable cleaning of drainage piping in the direction of drainage flow. [Ref. IPC 2018 Sec. 708.1.8]

Sheet P2.0

1. Please provide a label for the grade clean-out on the underground plan. [Ref. IPC 2018 Sec. 708.1.3]


ELECTRICAL COMMENTS

General

1. Please include the light pole footing design in the structural plan-set as this is addressed by the structural engineer of record.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
11/22/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0224-00307 - TD-DEV-0224-00042
5515 E Grant Rd. - C-2
New Car Wash (Revision 3, 1st Review)

TRANSMITTAL DATE: ‎November 22, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). Automotive Service and Repair - Automotive Washing - Self Service is a permitted use in the zone (UDC Table 4.8-4).

1. COMMENT: Zoning has reviewed the building plan for compliance with TD-DEV-0224-00042, and although it appears that the plans match, Zoning cannot approve the building plans until the revision to the DP is approved by all review agencies.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
11/12/2024 Fire New Construction REVIEW COMPLETED
10/30/2024 PDSD Application Completeness Express REVIEW COMPLETED