Permit Number: TC-COM-0224-00306
Parcel: 117150010

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0224-00306
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2024 External Reviewers - SAFEBuilt APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 6/23/2024 1:32:21 PM






Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 6/19/2024 11:28:19 AM




Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved with Comments
Reason:
Date Completed : 7/28/2024 7:24:17 PM
Second Revised plan plumbing review: OK see uploaded Pima Letter allowing grease interceptor change
RESOLVED-1). Plan pages P102 & P501: The revised grease interceptor from 1250 to 500 gallons is undersized per the Pima gravity grease interceptor sizing table located within the Tucson Plumbing code amendments. Update the plans with a
grease interceptor sized per the Pima gravity grease interceptor sizing table located within the Tucson Plumbing code amendments. or provide a letter from the utility Authority authorizing a 500 gallon grease interceptor to be utilized.
07/29/2024 Bldg Permits - Post Review REVIEW COMPLETED
07/24/2024 PDSD Application Completeness REVIEW COMPLETED