Permit Number: TC-COM-0224-00306
Parcel: 117150010

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0224-00306
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2024 Site Zoning APPROVED
07/23/2024 Water - PDSD APPROVED
07/23/2024 Site Engineering NOT REQUIRED
07/23/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/26/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 6/24/2024 10:39:29 PM
Revised plan plumbing review:
1). Plan pages P102 & P501: The revised grease interceptor from 1250 to 500 gallons is undersized per the Pima gravity grease interceptor sizing table located within the Tucson Plumbing code amendments. Update the plans with a grease
interceptor sized per the Pima gravity grease interceptor sizing table located within the Tucson Plumbing code amendments. or provide a letter from the utility Authority authorizing a 500 gallon grease interceptor to be utilized.
06/24/2024 Fire New Construction REVIEW COMPLETED
06/18/2024 PDSD Application Completeness REVIEW COMPLETED