Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0224-00306
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/12/2024 | Site Zoning | APPROVED | |||
07/23/2024 | Water - PDSD | APPROVED | |||
07/23/2024 | Site Engineering | NOT REQUIRED | |||
07/23/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/26/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 6/24/2024 10:39:29 PM Revised plan plumbing review: 1). Plan pages P102 & P501: The revised grease interceptor from 1250 to 500 gallons is undersized per the Pima gravity grease interceptor sizing table located within the Tucson Plumbing code amendments. Update the plans with a grease interceptor sized per the Pima gravity grease interceptor sizing table located within the Tucson Plumbing code amendments. or provide a letter from the utility Authority authorizing a 500 gallon grease interceptor to be utilized. |
||
06/24/2024 | Fire New Construction | REVIEW COMPLETED | |||
06/18/2024 | PDSD Application Completeness | REVIEW COMPLETED |