Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0224-00305
Parcel: 13217130A

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0224-00305
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2024 Site Zoning APPROVED
05/24/2024 Bldg Permits - Post Review REVIEW COMPLETED
05/24/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 5/24/2024 11:34:03 AM



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 2/21/2024 12:00:01 PM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 5/24/2024 10:20:27 AM
1. (RESOLVED) - Plan Sheet M200 - Provide Ventilation for Battery storage areas 162.1A and 162.2A - 2018 IMC Section [F} 502.5 and Table 403.3.1.1

2. (RESOLVED) - General - Provide Ventilation Calculations/Schedule for all new occupied areas - 2018 IMC Section Table 403.3.1.1 Minimum Ventilation Rates

3. (RESOLVED) - General - Provide ComCheck Mechanical Compliance Certificate - 2018 IECC Section C403.2.3 HVAC Equipment Performance Requirements

4. (RESOLVED) - General - Provide Duct Smoke Detectors in all units supplying a Design Capacity of more than 2000 CFM - 2018 IMC Section 606 Smoke Detection System Control 606.2.1 and 606.2.2



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved with Comments
Reason:
Date Completed : 5/24/2024 9:28:27 AM
1. Need to submit an interior lighting COMcheck for interior lighting.

a. COMcheck for interior lighting has been completed and attached. Resolved

2. E200 Electrical Lighting Plan: Need to provide circuit information for lighting.
a. See provided circuit information for lighting. Resolved, comment only: Circuits in Data Hall B are covered by the lighting fixtures.

3. E201A Electrical Power Plan Alt.: Missing Keynote 6.

a. Renamed sheet to “E201 – Electrical Power Plan”, see added ERU-1 in Corridor 171. Resolved

4. E202 Electrical Roof Plan: Need to provide circuit information.

a. See provided circuit information for rooftop receptacles. Resolved

5. E203 Electrical Grounding Plan: Extra Keynotes carried over from E201A.

a. Removed extraneous keynotes. Resolved

6. E204 Electrical Site Plan: Need to provide circuit information for new electrical equipment ie powered gates, lights.

a. Sheet removed from set. Resolved

7. E300 Electrical Schedules: Need to provide wire conductor size for any equipment not shown by Motor, Appliance, and Equipment Schedule i.e. site lighting or other equipment not specifically called out in schedule.

a. Added ERU-1 to motor list. Resolved

b. Wire conductor size for equipment not specifically called out in schedule is addressed in spec section 26 05 19 - 2.01 – C. Resolved

8. Confirm CRAC units 6, 9, 10, 11, 13, and 15 conductor feeds (currently #4) are adequate and meet NEC 430.22 requirements.

a. Conductor sizes for CRAC units have been verified with the manufacturer. Resolved