Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0224-00305
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/14/2024 | Site Engineering | NOT REQUIRED | |||
03/18/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/08/2024 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Denied Reason: Date Completed : 3/3/2024 8:55:52 PM 1. GENERAL - UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds. Please provide a written response to each comment; updates without a clear response to all comments may not be reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in additional comments. 2. S1 - DESIGN ASSUMPTIONS: The following structural design information shall be included in the construction documents per 2018 IBC Section 1603. Please include the following items in the structural general notes. i. Risk category ii. Wind design data a. Wind speed, Vult b. Exposure category c. Design wind pressures for exterior component and cladding materials, expressed in psf iii. Seismic design data a. Seismic importance factor, Ie b. Site class c. Mapped spectral response acceleration parameters, Ss and S1 d. Design spectral response acceleration parameters, SDS and SD1 e. Seismic design category f. Analysis procedure used 3. S1 - STATEMENT OF SPECIAL INSPECTIONS: The structural general notes provide information on special inspections that appears incomplete. Per the 2018 International Building Code, Section 1704.2.3, along with the construction documents, the applicant shall submit a Statement of Special Inspections as a condition for permit issuance. A full list of what this statement shall include is provided in IBC Section 1704.3.1. Highlights include: i. Statement shall identify the materials and work required to have special inspections or tests, ii. The type and extent of each inspection, and iii. Identification as to whether each inspection shall be performed continuously or periodically, as defined by the IBC. Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 2/21/2024 12:00:01 PM Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 3/4/2024 11:52:36 PM 1. Plan Sheet M200 - Provide Ventilation for Battery storage areas 162.1A and 162.2A - 2018 IMC Section [F} 502.5 and Table 403.3.1.1 2. General - Provide Ventilation Calculations/Schedule for all new occupied areas - 2018 IMC Section Table 403.3.1.1 Minimum Ventilation Rates 3. General - Provide ComCheck Mechanical Compliance Certificate - 2018 IECC Section C403.2.3 HVAC Equipment Performance Requirements 4. General - Provide Duct Smoke Detectors in all units supplying a Design Capacity of more than 2000 CFM - 2018 IMC Section 606 Smoke Detection System Control 606.2.1 and 606.2.2 Electrical(E) Reviewer Ron Ross rross@safebuilt.com Denied Reason: Date Completed : 3/4/2024 11:09:45 AM Electrical Review of Involta By: Ron Ross PE Need to submit an interior lighting comcheck for interior lighting. E200 Electrical Lighting Plan: Need to provide circuit information for lighting. E201A Electrical Power Plan Alt.: Missing Keynote 6. E202 Electrical Roof Plan: Need to provide circuit information. E203 Electrical Grounding Plan: Extra Keynotes carried over from E201A. E204 Electrical Site Plan: Need to provide circuit information for new electrical equipment ie powered gates, lights. E300 Electrical Schedules: Need to provide wire conductor size for any equipment not shown by Motor, Appliance, and Equipment Schedule i.e. site lighting or other equipment not specifically called out in schedule. Confirm CRAC units 6, 9, 10, 11, 13, and 15 conductor feeds (currently #4) are adequate and meet NEC 430.22 requirements Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 3/6/2024 12:22:21 AM First Plumbing Review: 1). Non potable water piping on plan page M202 needs to be identified and installed per -2018 IPC 608.9 2). What is the use of the new Potable water piping shown on plan page M202? -2018 IPC 608.3 3).Keynote 8 location on Plan page M202 doesn't correlate with piping it is adjacent to? -2018 IPC 106.3.4). 4). Plan page M202 needs to illustrate the sump pump's sewer tie in location as stated on plan page M301 detail 4 -2018 IPC 106.3.1 5). Plan page M202 needs to illustrate the sump pump's vent tie in location as stated on plan page M301 detail 4 -2018 IPC 106.3.1 |
||
03/18/2024 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: TC-COM-0224-00305 1215 E Pennsylvania St. Tucson, AZ. 85714 (1st Review) TRANSMITTAL: March 18, 2024 Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the I-1 zone (UDC 4.7.21). 1. Identify the Use for the property per the City of Tucson UDC Article 4.8.7. Provide a note on the Cover Sheet stating the use of the property. 2. The Site Plan provided shows proposed site additions that require a development package. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf. There is a previously approved Development Package for the site (link below) that can be used as an example of what can be submitted- https://pro.tucsonaz.gov/permitdetails/DP19-0168/ 3. A permit associated with previously approved Development Package, related to a new antenna installation was never finalized. There are still outstanding inspections. Permit T19CM07099 will need to be finalized before further permits will be issued for the property. If you have any questions about this transmittal, please contact Nathan.Herrera@tucsonaz.gov. |
||
03/13/2024 | Fire New Construction | REVIEW COMPLETED | |||
02/16/2024 | PDSD Application Completeness | REVIEW COMPLETED |