Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0224-00296
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/04/2024 Commercial Building APPROVED
02/28/2024 Commercial Electrical APPROVED
03/06/2024 Commercial Plumbing APPROVED
02/13/2024 Site Zoning APPROVED
03/05/2024 Water - PDSD APPROVED
02/27/2024 Site Engineering NOT REQUIRED
03/06/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/06/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Clarify the balancing information for HP-3: only 900 CFM of supply is identified. Reference: Section 107.2.1, IBC 2018.
2. Provide an exhaust duct for a possible clothes dryer collocated with the proposed clothes washer. Reference: Section 504.8.6, IMC 2018.
02/26/2024 Fire New Construction REVIEW COMPLETED
02/13/2024 PDSD Application Completeness Express REVIEW COMPLETED