Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0224-00296
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/04/2024 | Commercial Building | APPROVED | |||
| 02/28/2024 | Commercial Electrical | APPROVED | |||
| 03/06/2024 | Commercial Plumbing | APPROVED | |||
| 02/13/2024 | Site Zoning | APPROVED | |||
| 03/05/2024 | Water - PDSD | APPROVED | |||
| 02/27/2024 | Site Engineering | NOT REQUIRED | |||
| 03/06/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/06/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Clarify the balancing information for HP-3: only 900 CFM of supply is identified. Reference: Section 107.2.1, IBC 2018. 2. Provide an exhaust duct for a possible clothes dryer collocated with the proposed clothes washer. Reference: Section 504.8.6, IMC 2018. |
||
| 02/26/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 02/13/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |