Permit Number: TC-COM-0224-00291
Parcel: 116124830

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0224-00291
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2024 Site Engineering NOT REQUIRED
03/25/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/25/2024 Commercial Structural REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0224-00291
ADDRESS/PARCEL: (1460 W SAINT MARYS RD TUCSON, AZ 85745)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. Please coordinate with the Zoning Department, ensure that you process the Request for Zoning Authority Clearance & submit your response.
2. Submit a complete Egress Plan. Indicate the travel distances and the number of people exiting at each exit.
3. We understand that the Occupancy Classification is R4 (ensure that your selection confirms what you selected from the City Zoning Code & your State License Application).
4. Please do complete your Code Analysis. Do the clients reside at the facility on a 24-hour basis? Include a statement as part of your code analysis as to how the facility handles any persons receiving custodial care who require limited verbal or physical assistance responding to an emergency situation to complete building evacuation and self preservation. Specify Condition 1 or Condition 2 per IBC 310 (this will determine the type of fire sprinkler system the fire department will require).
5. On the Site Plan show/indicate the Accessible route from drop off location to the accessible entry door complying to IBC 106 & ANSI A117.
6. In an Emergency, show/locate the gathering area/dispersal area where it is safe from danger minimum 50 ft away from structure per IBC 310.5 and 1028.5. 2.)
7. Indicate the clear opening of the doors complying to ANSI A117.
8. Indicate the clear width of hallways.
9. Show/locate the side & back grab bars at the Water Closet as well as at the Shower, make sure to indicate the installation of Structural Backer Board for these grab bars per IBC Chapter 11. 5.)
10. Provide Emergency Escape & Rescue Openings per R310 at every bedroom/sleeping space. On the drawing adjacent to the opening(s), indicate the clear opening for both horizontally and vertically and provide the dimension from the finish floor to the bottom of the opening. Indicate if there are obstacles on either side of the opening.
11. Fire Sprinkler is required per IBC 420 and processed as a separate permit. Submit the drawings to Tucson Fire Department for review and approval. They will conduct fire inspection, the inspection approval document will be required as a deferred submittal before issuing the Certificate of Occupancy.
12. A fire alarm if applicable per [IBC 907], If they exist...indicate them on your drawing.
13. Illumination with emergency backup power is required in all components of the means of egress system [IBC 1008]. Please locate those equipments including the lighted exit sign(s) on your plan (to be inspected by Tucson Fire Department).
14. Electrical work (conductors/wiring/breaker ONLY) related to the installation of Emergency Lights, Lighted Signs, Fire/Audible/Smoke Alarms/Fire Extinguisher will be inspected by City of Tucson inspectors, show on your plans so that our inspectors will know what wiring/breaker to inspect and shall also be reviewed as part of this permit. Any new renovation work must be included as part of this building permit.
15. An Operator's License must be applied for with the State, the absence of this license shall void this building permit.
16. Submit a draft copy of the State License application confirming the exact use title for the certificate of occupancy document.
17. Please resubmit.
03/20/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: Nathan Herrera
Planner

PROJECT: TC-COM-0224-00291
1462 W Saint Mary's Road– C-1
Duplex to Behavioral Health (1st Review)

TRANSMITTAL DATE: March 20, 2024

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Per UDC Article 11.4.20, A Site is defined as, The land area consisting of a portion of a lot, an entire lot, or contiguous lots, designated for development as a single entity. The site is made up of two existing duplexes. The proposed change in use of the property from will require a Development Package (UDC 3.3.3.G.2.c). The Development Package is a separate submittal and shall be approved prior to approval of this building permit and the related permit TC-COM-0224-00304.



If you have any questions about this transmittal, please contact me at Nathan.Herrera@tucsonaz.gov or at 520-837-4894.
03/14/2024 Fire New Construction REVIEW COMPLETED
02/21/2024 PDSD Application Completeness Express REVIEW COMPLETED