Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0224-00289
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/14/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/14/2024 | Commercial Electrical | REQUIRES RESUBMIT | Permit Review TC-COM-0224-00289 (4004 S PARK AV TUCSON, AZ 85714) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Specify the specific EV model numbers being used at EV1 and EV2, IBC 107.1. Multiple specification sheets have been provided, but it’s not clear which models are being used. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
02/13/2024 | PDSD Application Completeness | REVIEW COMPLETED |