Permit Number: TC-COM-0224-00284
Parcel: 117120360

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0224-00284
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/29/2024 Commercial Building APPROVED
03/05/2024 Commercial Mechanical APPROVED
02/14/2024 Site Zoning APPROVED
02/27/2024 Site Engineering NOT REQUIRED
03/05/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/28/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Indicate branch circuit numbers and panel designations for all power and lighting in the electrical floor plans. NEC 408.4.

2 Show the location of the breaker panel serving the area of the TI.

3 Provide a complete luminaire schedule and compliance with thee 2018 IECC for lighting if applicable.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC.
02/21/2024 Fire New Construction REVIEW COMPLETED
02/12/2024 PDSD Application Completeness REVIEW COMPLETED