Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0224-00284
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/29/2024 | Commercial Building | APPROVED | |||
03/05/2024 | Commercial Mechanical | APPROVED | |||
02/14/2024 | Site Zoning | APPROVED | |||
02/27/2024 | Site Engineering | NOT REQUIRED | |||
03/05/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/28/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Indicate branch circuit numbers and panel designations for all power and lighting in the electrical floor plans. NEC 408.4. 2 Show the location of the breaker panel serving the area of the TI. 3 Provide a complete luminaire schedule and compliance with thee 2018 IECC for lighting if applicable. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC. |
||
02/21/2024 | Fire New Construction | REVIEW COMPLETED | |||
02/12/2024 | PDSD Application Completeness | REVIEW COMPLETED |