Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0224-00274
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/04/2024 | Commercial Mechanical | APPROVED | |||
03/04/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/21/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Ref; Plan Sheet M4.1and E6.1. The CHILLER SCHEDULE calls out for 500-amp fuses... The Mechanical plan reviewer concurred. The electrical plan sheet calls for utilizing the existing 400 amp fused disconnect, fuse size not specified, and the existing 400-amp circuit breaker in the SWITCHBOARD. The fuse sizes shown in the Equipment Schedule are sized to prevent nuisance tripping, per Mechanical plan Reviewer and NEC art 440.22.... Please revise the electrical plan in order to provide the necessary overcurrent protection or justify utilizing the existing 400 amp disconnect switch and SWITCHBOARD 400-amp breaker. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
02/09/2024 | PDSD Application Completeness | REVIEW COMPLETED |