Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0224-00261
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/09/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
05/09/2024 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | The air balance report shows that the two restroom exhaust fans, EF-1 and EF-2, are not providing adequate ventilation. The minimum requirement is 50 CFM per water closet but the two fans are only moving 36 CFM and 34 CFM respectively. Reference: Section 403.3.1.1, IMC 2018. | ||