Permit Number: TC-COM-0224-00255
Parcel: 107112090

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0224-00255
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2024 Commercial Mechanical APPROVED
03/18/2024 Site Zoning APPROVED
03/13/2024 Water - PDSD APPROVED
03/05/2024 Site Engineering NOT REQUIRED
03/18/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/18/2024 External Reviewers - Stantec REQUIRES RESUBMIT February 13, 2024
1st Review

David E Shambach, Architect, Inc.
Attn: Rich Lovato
1202 E. Broadway Blvd., Studio 112
Tucson, Arizona 85719

Re: HALO DISPENSARY
REMODEL

City of Tucson Permit Number: TC-COM-0224-00255
Stantec Project Number: 185215066
Stantec File Number: TUC-24-012

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. To facilitate a shorter back-check time, we request that you please, only provide plans and calculation pages that have been revised, clouding any changes, along with a written response to each of the noted items indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M V-B 6,469 65 No No
Separate Permits: Signage.
Deferred Submittals: None.
Special Inspections: Concrete, epoxy and expansion anchors, field welding, masonry, structural steel.

ARCHITECTURAL COMMENTS

General

1. Note on the cover of the drawings that special inspection is required for concrete, epoxy and expansion anchors, structural steel, field welding, masonry. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet A1.4

1. Please provide roof drain flow rate calculations and sizes of the new proposed roof drains for the modified sections of roof. [Ref. IPC 2018 Sec. 1106]

Sheet A4.0

1. A turning space is required within all accessible toilet rooms. The proposed bathrooms do not indicate a turning space. Please revise. [Ref. ICC A117.1-2009 Sec.603.2.1]

STRUCTURAL COMMENTS

Sheet S1.0

1. The construction documents and structural calculations are conflicting. Note 1 under the concrete section of the general notes indicates that the concrete is designed to 2,500 psi but the foundation calculations indicate the design strength at 3,000. Please clarify and revise. [Ref. IBC 2018 Sec. 1705.3]

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

Sheet P2.0

1. The faucets indicated for the lavatories are two handle. In accordance with Section 419.6 of the 2018 International Plumbing Code as amended by the city of Tucson, all new or replacement faucets serving lavatories in all buildings other than Group R3 occupancies, individual units in Group R2 occupancies, or International Residential Code Structures shall be provided with automatic faucets.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/04/2024 Fire New Construction REVIEW COMPLETED
02/07/2024 PDSD Application Completeness Express REVIEW COMPLETED