Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.4
Permit Number - TC-COM-0224-00249
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/25/2024 | Commercial Mechanical | APPROVED | |||
06/25/2024 | Commercial Structural | APPROVED | |||
06/25/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/25/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Provide a secondary roof scupper at the east side of the new roof (where the 12” x 12” scupper is now). [Initial comment: Show the secondary roof scuppers; provide a detail showing how they are to be installed. Note: Detail 8/A1.7 does not meet the requirements of Section 1108.1, IPC 2018. Reference: Section 1101.7 and 1102.2, IPC 2018 and Section 1611.1, IBC 2018.] | ||
06/25/2024 | Fire New Construction | REVIEW COMPLETED | |||
06/18/2024 | PDSD Application Completeness | REVIEW COMPLETED |