Permit Number: TC-COM-0224-00245
Parcel: 10818716A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0224-00245
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2024 Site Zoning APPROVED
03/12/2024 Water - PDSD APPROVED
02/29/2024 Site Engineering NOT REQUIRED
03/14/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
03/14/2024 External Reviewers - Stantec REQUIRES RESUBMIT February 9, 2024
1st Review

Joesler Village Tucson, LLC
Attn: Karen Wolf
555 E. River Road, Suite 201
Tucson, Arizona 85704

Re: TUCSON, ARIZONA 85704
PSOMAS - REMODEL

City of Tucson Permit Number: TC-COM-0224-00245
Stantec Project Number: 185215066
Stantec File Number: TUC-24-011

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. To facilitate a shorter back-check time, we request that you please, only provide plans and calculation pages that have been revised, clouding any changes, along with a written response to each of the noted items indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 11,450 76 Yes No
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system modification [2018 IBC Sec. 903] is to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

General

1. Please provide energy conservation compliance reports for the new mechanical units indicated. [Ref. IECC 2018 C403.3.2]

Sheet M-4

1. The outside air ventilation calculations table is missing the “IT Room” O.A. ventilation calculations. [IMC 2018 Table 403.3.1.1]

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

Sheet E4.0

1. The one-line diagram and panel schedules have conflicting information for Panels P, P1, P2, and M. The one-line indicates that the panels are all MCB, but the panel schedules show them as MLO. Please clarify and revise. [Ref. NEC 2017 Art. 240]

2. The one-line diagram and panel schedules have conflicting information for Panel P. The one-line diagram indicates Panel P with a 400-amp bus and the panel schedule indicates the panel as 200-amp. Please clarify and revise.

3. The fault current calculations and panel schedules have conflicting information for panels P, P1, P2, and M. The fault current calculations indicate the AIC rating of the panels as 42,000 but the panel schedules indicate the AIC rating as 22,000. Please clarify and revise.

4. The feeder schedule is missing feeders for Panel P2. Please revise.

5. Please indicate the fault current analysis marks on the one-line diagram.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
02/29/2024 Fire New Construction REVIEW COMPLETED
02/06/2024 PDSD Application Completeness REVIEW COMPLETED