Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0224-00231
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/16/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/16/2024 | Air Balancing/Commissioning Report (Deferred Submittal) | REQUIRES RESUBMIT | 1. Please have Registrant of Record provide a Sealed letter indicating how to proceed with the below issues. (1) THERE WERE NO REQUIRED CFM VALUES LISTED FOR THE TERMINALS. THERE IS ALSO NO BALANCING DAMPERS INSTALLED FOR ANY OF THE TERMINALS. (2) THE EXISTING RTU IS AT MAXIMUM SPEED WITH CLEAN FILTERS. THE AIRFLOW IS SET AS HIGH AS POSSIBLE. * MEASURED WITH ZONE DAMPERS 1 AND 2 100% OPEN AND THE BYPASS DAMPER FULLY CLOSED. Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
08/15/2024 | PDSD Application Completeness | REVIEW COMPLETED |