Permit Number: TC-COM-0224-00230
Parcel: 124050520

Review Status: Requires Resubmit

Review Details: COMMERCIAL FENCE/WALL v.1

Permit Number - TC-COM-0224-00230
Review Name: COMMERCIAL FENCE/WALL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/20/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.

1. Please provide an architectural site plan to include the project address. IBC 107.2

2. Please provide construction drawings to include and structural calculations prepared by an Arizona licensed design professional for the two 8' tall intermediate posts to include the foundation system. Additionally provide the width of all openings. City of Tucson submittal requirements and IBC 107.2



Mark Masek

Plans Examiner

Mark.masek@tucsonaz.gov

520-837-4994
02/20/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response
1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical lighting plans for the exterior lighting, design, and calculations, sealed by an Arizona Registrant.
Provide complete compliance with the 2012 City of Tucson Outdoor Lighting Code. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
02/09/2024 Site Engineering REQUIRES RESUBMIT See zoning comment
02/05/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0224-00230
820 E UNIVERSITY BL. – HC-1
New site fencing ( 1st Review)

TRANSMITTAL: February 5, 2024
This site is located in the HC-1 zone (4.7.20 ).

1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.

COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).

2. Historic review is required and must be approved prior to approval of this building plan. Historic application/requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Historic-Preservation

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
02/02/2024 PDSD Application Completeness REVIEW COMPLETED