Permit Number: TC-COM-0224-00221
Parcel: 10509550A

Address:
4881 N STONE AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0224-00221
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2024 Site Zoning APPROVED
02/27/2024 Site Engineering NOT REQUIRED
02/27/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
02/21/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 2/15/2024 8:00:36 PM
Proposed scope of work does not appear to impact the existing structure. No review required.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Denied
Reason:
Date Completed : 2/14/2024 2:16:49 PM
1. Sheet A1.10 (Floor Plan): Provide clarification regarding the adjacent tenants to ensure proper tenant separation. Provide clarification regarding the existing building and separated mix use/non-separated mix use in accordance with 2018 IBC Section 508.

2. Sheet G1.10 (Life Safety Plan): The means of egress travels through a pickleball court, however, there are gates in that path. Gates must comply with 2018 IBC Section 1010.2, thus, panic and fire exit hardware would be required on the gates in accordance with 2018 IBC Section 1010.1.10. Provide all applicable details and updated door hardware schedule.

3. Sheet G2.10 (Signage Location Plan): The exit that is accessed through the pickleball court is missing the proper exit signage. Provide the correct exit signs in accordance with IBC 2018 Section 1013.

4. Sheet A1.11 (Enlarged Floor Plan): At least 5% of each type of locker is required to be accessible. Provide the proper number of accessible lockers along with applicable details in accordance with the 2010 ADAAG Section 222.1.

5. Sheet A5.30 (Check-In Counter Section): The checking counter does not have a portion that is accessible. Provide an accessible portion of the check in counter in accordance with 2010 ADAAG Section 902.3.



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 2/16/2024 10:23:24 AM
1. General - Provide RTU Specification Schedule - 2018 IBC Section [A]107.2.1Information on construction documents - Confirm O/A Quantities match Ventilation Schedule.

2. General - Provide ComCheck Mechanical Compliance Certificate - 2018 IECC Section C103.2 Information on Construction Documents

3. General - Current use has been changed to A-3 Assembly. Confirm a Rational Smoke Analysis Report is not required.
- NFPA 92 - 2018 IBC Section 909 Smoke Control Systems



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 2/12/2024 11:58:23 AM
Electrical Review of ACE Pickleball Club
By: Ron Ross PE
E2.10 POWER PLAN: Need to call out GFI protection for ECW-1. Ie electric water fountains need GFI protection per NEC 422.5. Could provide GFI circuit breaker in panel instead or receptacle for difficult to access GFI receptacle.




Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 2/18/2024 7:02:02 PM
First Plumbing Review:
1). add lavatory side wall & lavatory to lavatory center to center separations measurements to plan page A6.10. -2018 IPC 405.3.1

2). Add water closet compartment measurements & fixture center distances to plan page A6.10 - 2018 IPC 405.3.1

2). Add Urinals to Provided Fixture counts on plan page G1.10 -2018 IPC 403.1
02/27/2024 Fire New Construction REQUIRES RESUBMIT -Indicate in the code analysis and deferred submittals that a fire alarm per NFPA will be installed. IFC 907.2.1
-Update door hardware details indicating the required panic hardware on all exit doors. IFC 1010.1.10
john.vincent@tucsonaz.gov
5203495581
02/02/2024 PDSD Application Completeness REVIEW COMPLETED