Permit Number: TC-COM-0224-00221
Parcel: 10509550A

Address:
4881 N STONE AV

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0224-00221
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2024 Bldg Permits - Post Review REVIEW COMPLETED
03/12/2024 External Reviewers - SAFEBuilt REVIEW COMPLETED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 2/15/2024 8:00:36 PM
Proposed scope of work does not appear to impact the existing structure. No review required.



Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 3/8/2024 10:30:10 AM



Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 3/7/2024 6:11:53 PM
1. General - Provide RTU Specification Schedule - 2018 IBC Section [A]107.2.1Information on construction documents - Confirm O/A Quantities match Ventilation Schedule. (RESOLVED)

2. General - Provide ComCheck Mechanical Compliance Certificate - 2018 IECC Section C103.2 Information on Construction Documents (RESOLVED)

3. General - Current use has been changed to A-3 Assembly. Confirm a Rational Smoke Analysis Report is not required. - NFPA 92 - 2018 IBC Section 909 Smoke Control Systems. (RESOLVED)



Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 3/7/2024 8:19:42 AM



Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 3/9/2024 11:13:11 AM
Second Plumbing Review:OK
Resolved 1). add lavatory side wall & lavatory to lavatory center to center separations measurements to plan page A6.10. - 2018 IPC 405.3.1

Resolved 2). Add water closet compartment measurements & fixture center distances to plan page A6.10 - 2018 IPC 405.3.1

Resolved 3). Add Urinals to Provided Fixture counts on plan page G1.10 -2018 IPC 403.1
03/22/2024 Fire New Construction REVIEW COMPLETED
03/06/2024 PDSD Application Completeness REVIEW COMPLETED