Permit Number: TC-COM-0223-00696
Parcel: 13101002F

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0223-00696
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2023 Commercial Plumbing APPROVED
04/11/2023 Commercial Structural APPROVED
03/24/2023 Site Engineering NOT REQUIRED
03/22/2023 Site Zoning NOT REQUIRED
04/11/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
03/27/2023 Commercial Electrical REQUIRES RESUBMIT Please address the plan review comments and provide a written response.

This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.

1 Show all pool electrical equipment locations, pumps, heaters, devices, and receptacles, etc. Correlate equipment power requirements and circuit designations with the Pool Power panel and panel schedule.

2 Provide a wiring diagram and show the locations for the disconnecting switches/devices for the pool and spa as required per NEC art 680.13 and 680.41.

3 Verify compliance with the 2012 City of Tucson Outdoor Lighting Code for the pool Lighting. See OLC Chapter 4 and 401.2.1(2).

4 Show all grounding required for the Pool and Spa, per NEC art 680.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.
03/07/2023 Fire New Construction REVIEW COMPLETED