Permit Number: TC-COM-0223-00696
Parcel: 13101002F

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-0223-00696
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
06/12/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Per the response letter May 10, 2023. "Please see resubmitted plans, which have been signed and stamped by an Arizona-licensed electrical engineer”.

The resubmitted plans are stamped by a Mechanical Engineer, DR ILDEFONSO GONZALEZ. Please clarify.

2 Provide complete electrical and lighting floor plans showing locations of the pool equipment, lighting and receptacles, branch circuit and panel designations that correlate with the panel schedule, NEC 408.4 designated ‘Maintenance Disconnecting Means’ NEC 680.13, ‘Emergency Switch’ NEC 680.41, ‘125-volt Receptacle NEC 680.22(A)’. Also provide wiring diagrams for the Emergency and Maintenance Disconnect.

3 Provide complete compliance with the City of Tucson Outdoor Lighting Code for the exterior Pool/Spa area lighting per section 104 (Outdoor lighting submittal requirements). Include exterior and interior pool lighting curfew requirements.

4 Provide a complete luminaire schedule. Include lamp color temperature and lumen output information.

Ref’ 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.
05/22/2023 PDSD Application Completeness REVIEW COMPLETED