Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0223-00690
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/08/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/08/2023 | Commercial Building | REQUIRES RESUBMIT | Please respond to the following: 1. Please provide structural calculation on the steel members being used for this 8 foot steel fence and gate. 2. Is gate swinging or sliding. Provide proper supporting post size for the swinging gate with structurally calculated/correct footing/caisson size. 3. Provide structural calculation for the correct size of the fence footing for an 8 ft tall steel fence resisting lateral forces such as a 115 mph gust of wind. 4. Is gate operated electrically. If so, provide electrical information, 5. Please resubmit. |
||
| 06/05/2023 | Fire New Construction | REVIEW COMPLETED | |||
| 06/02/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |