Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0223-00685
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/06/2023 | Commercial Electrical | APPROVED | |||
| 06/12/2023 | Commercial Mechanical | APPROVED | |||
| 06/12/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/12/2023 | Commercial Plumbing | REQUIRES RESUBMIT | The water calculations actually show an allowable pressure drop of 20.19 PSI for pipe friction. The minimum pressure at the end of the piping run would be only 8 PSI using your calculations. [Initial comment: Verify that the specified water closet will have sufficient water pressure to operate properly. The manufacturer requires a minimum flowing water pressure of 20 PSI for proper operation. Reference: Section 303.2, IPC 2018.] | ||
| 05/09/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |