Permit Number: TC-COM-0223-00685
Parcel: 124170390

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0223-00685
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2023 Commercial Electrical APPROVED
06/12/2023 Commercial Mechanical APPROVED
06/12/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/12/2023 Commercial Plumbing REQUIRES RESUBMIT The water calculations actually show an allowable pressure drop of 20.19 PSI for pipe friction. The minimum pressure at the end of the piping run would be only 8 PSI using your calculations. [Initial comment: Verify that the specified water closet will have sufficient water pressure to operate properly. The manufacturer requires a minimum flowing water pressure of 20 PSI for proper operation. Reference: Section 303.2, IPC 2018.]
05/09/2023 PDSD Application Completeness Express REVIEW COMPLETED