Permit Number: TC-COM-0223-00667
Parcel: 116210220

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0223-00667
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2023 Historic NOT REQUIRED
04/02/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/23/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0223-00667

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
Denied
1. Sheet TS: The occupant load for the tap room is calculated incorrectly. It appears that there is fixed seating (booths or benches) present and should be calculated appropriately. Provide a corrected occupant land in accordance with Section 1004.6.
2. At least 5% of the dining surfaces including that bar are required to have mobility features. Provide calculations of the required amount of accessible seating and indicate the locations. Additionally, ensure that surfaces are properly dispersed throughout the structure. Section 226.1 and 226.2 of the 2010 ADAAG.


MECHANICAL REVIEW COMMENTS:
Denied
1. Provide a detailed kitchen equipment schedule.
2. Provide all manufacturer specifications for the pizza oven for review.


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review: BLDG #2
1). Show roof drain conductor sizes on plan page P1.0. -IPC 1106.2 (only shows roof drain sizes)
2). Show the accessible route with distances to the plumbing restrooms that will serve this building. -IPC
3). Plan page P1.0 Detail #1 states water & Gas plan, no gas system is shown? -IFGC 106.3.1
4). BLDG #2 Hose Bibs on plan page P1.0 need shut off valves-IPC 606.2
5). Bldg. #2 needs a service sink -IPC 403.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/24/2023 Site Engineering REQUIRES RESUBMIT See zoning comments
03/22/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0223-00667
1000 W Congress St. – C-1 (1st Review)

TRANSMITTAL: March 22, 2023, 2023
This site is located in C-1 zone (UDC 4.7.20). Food Service is a permitted use in the zone, (Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 & 5 and 4.9.13.O.

1. Zoning has reviewed the plan for compliance with development package (DP) TD-DEV-1222-00074 but until the DP has been approved by all review agencies Zoning cannot approve this plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
03/23/2023 Fire New Construction REVIEW COMPLETED
03/01/2023 PDSD Application Completeness Express REVIEW COMPLETED