Permit Number: TC-COM-0223-00665
Parcel: 103090800

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0223-00665
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2023 Site Zoning APPROVED
03/20/2023 Site Engineering NOT REQUIRED
03/24/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
03/24/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0223-00665


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1) Show all fire-rated assemblies for storage and production of hazardous material areas and mixed-use separation on the floor plan.
2) Detail methods of storing hazardous materials per IFC 5704.3.
3) Detail means of spill containment.


BUILDING REVIEW COMMENTS:
Denied
1) Need the COMcheck energy compliance report for new envelope insulations, doors, and windows, mechanical, interior and exterior lights.
2) Show all fire-rated assemblies for storage and production of hazardous material areas and mixed-use separation on the floor plan.
3) Detail methods of storing hazardous materials per IFC 5704.3.
4) State items stored in room 108.
5) Detail means of spill containment.
6) Electrical equipment in electrical room does not have the required workspace.
7) Show locations of emergency eye-wash and shower stations. Include locations of fire extinguishers.


MECHANICAL REVIEW COMMENTS:
Denied
1) Need the COMcheck energy compliance report for new envelope insulations, doors, and windows, mechanical, interior and exterior lights.
2) Detail ventilation of the areas used for the storage and processing of the hazardous materials per IMC 510. Show exhaust locations on elevation views.
3) Detail duct dampers in rated assemblies per IMC 607.


ELECTRICAL REVIEW COMMENTS
Denied
1) Need the COMcheck energy compliance report for new envelope insulations, doors, and windows, mechanical, interior and exterior lights.
2) Detail electrical installation for classified locations for flammable liquid-produced vapors per NEC Article 500.
3) Electrical equipment in electrical room does not have the required workspace.


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/20/2023 Fire New Construction REVIEW COMPLETED
03/10/2023 PDSD Application Completeness REVIEW COMPLETED