Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0223-00652
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/27/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/27/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Verify that the replaced new Panel ‘HPA’ has a main breaker or provide a fused disconnect to provide overcurrent protection within 25’ of the transformer secondary connection.as required per NEC art 240.21(C), 408.36(B), and verify that the load of Panel ‘HPA’ does not exceed the ampacity of the branch circuit and OCPD provided via 7.5 KVA transformer and Panel ‘HLA’. 2 Provide a grounded Meal Cover for the Underground Concrete Junction Box. NEC 314.30(D), Detail 315/E2. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||