Permit Number: TC-COM-0223-00652
Parcel: 140420760

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0223-00652
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/27/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/27/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Verify that the replaced new Panel ‘HPA’ has a main breaker or provide a fused disconnect to provide overcurrent protection within 25’ of the transformer secondary connection.as required per NEC art 240.21(C), 408.36(B), and verify that the load of Panel ‘HPA’ does not exceed the ampacity of the branch circuit and OCPD provided via 7.5 KVA transformer and Panel ‘HLA’.

2 Provide a grounded Meal Cover for the Underground Concrete Junction Box. NEC 314.30(D), Detail 315/E2.

Ref; 2018 IBC section 107.2.1, 2017 NEC
03/02/2023 PDSD Application Completeness Express REVIEW COMPLETED