Permit Number: TC-COM-0223-00644
Parcel: 12701005D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0223-00644
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2023 Site Zoning APPROVED
03/30/2023 Site Engineering NOT REQUIRED
03/30/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
03/23/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0223-00644

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. AISI S240-15 - C3.4.3. Provide a slip track detail for the metal stud wall connection to the roof assembly. The plans indicate that the head-of-wall is connected directly to the roof system, and the wall studs are connected directly to the track, which will not allow for roof deflections.


BUILDING REVIEW COMMENTS:
Denied
1. 2018 IBC Table 601. Verify the correct construction type is noted on sheet G1 - General Building Summary. The table indicates type I-A construction, which is not common for this size and use of the building.
2. 2018 IBC Table 2902.1. Revise the plans or provide clarification that additional plumbing fixtures are not required. The existing "business" occupancy appears to have an existing occupant load of 12 (1,764 sqft/150) and the new occupant load is an increase of 23, for a total of 35 occupants. Verify the removal of the existing plumbing fixtures in the tenant space, and the use of the existing plumbing fixtures shared by other tenants, is sufficient given the increased occupant load.
3. 2009 ANSI A117.1 - 608.2.3.1. Revise the plans show that the minimum inside dimension of the alternate roll-in type showers is 3' clear. With the application of the tile finish and grout, this dimension will be less than the required 36" clear width.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Denied
1. 2017 NEC - 700.12(F)(2)(3). Revise the electrical plans to indicate that the emergency/exit lighting is tied to the local lighting circuit ahead of any switching devices.


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/21/2023 Fire New Construction REVIEW COMPLETED
03/09/2023 PDSD Application Completeness REVIEW COMPLETED