Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2023 Site Engineering NOT REQUIRED
04/03/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/23/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0223-00643


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. 2018 IBC 107.2.1. Revise sheet G1.2 - Detail 3 to include the depth of the footing and depth of bollard embedment.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Denied1. 2018 IBC 107.2.1. Clarification needed. Sheet A1.1 "Equipment Schedule" indicates that Q01## - Remote Condensing Unit is to be installed on the dining room roof; however, there is no information regarding this equipment and it does not clearly show on the floor plans. Provide the equipment specifications and location on the plans, or if it is not being used, eliminate the item from the schedule


ELECTRICAL REVIEW COMMENTS
Denied
1. 2018 IBC 107.2.1. Revise the electrical floor plans to show electrical circuitry, including the panel name and circuit number, that each outlet/appliance/equipment is connected to.
2. 2018 IBC 1008.3.2. Revise the plans to show emergency lighting on the exterior of the building at the landing for egress doors.
3. 2017 NEC 700.12(F)(2)(3). Revise the plans to indicate the emergency lighting units will be tied to the local lighting circuit, ahead of any switching devices.


PLUMBING REVIEW COMMENTS:
Denied
1. 2018 IPC - 608.1. Revise the plans to indicate the backflow prevention device for the beverage systems.
2. 2018 IPC - 1002.4. Revise the plans to include a trapped floor drain (if none exists) for the new drink stations, as referenced on sheet A1.1 - note #14.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/29/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-COM-0223-00643
5391 E SPEEDWAY BL Zoning C-2

TRANSMITTAL DATE:‎March 29, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Clarify if signage is being proposed with this permit, If signage is not being proposed provide a not that “signs are by separate permit”


If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
03/20/2023 Fire New Construction REVIEW COMPLETED
03/09/2023 PDSD Application Completeness Express REVIEW COMPLETED