Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0223-00635
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2023 Site Zoning APPROVED
03/29/2023 Site Engineering NOT REQUIRED
04/05/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/23/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0223-00635

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. 2018 IBC - Table 601. Clarification needed on construction type. and/or plans revised. Sheet G003 code data indicates type II-A construction type. Partition type "A" surrounds a primary structural column in the "Sales Area"; however, there is no fire resistance-rated designation as required for type II-A construction primary members. Verify if II-A construction is correct and revise the partition type; or, revise the construction type to be compliant with Table 601.
2. 2018 IBC - 1109.9 & 2009 ANSI A-117.1. Revise the plans to show that 5% of the storage lockers are accessible, and the hardware does not require a pinching or twisting motion.
3. 2018 IBC - 107.2.1. Revise the code data to include whether a fire alarm system is installed.
4. 2018 IBC - 107.2.1. Revise sheet A503 to eliminate the penetration details that are not relevant to this project.


MECHANICAL REVIEW COMMENTS:
Denied
1. 2018 IMC - 307.2.1, 307.2.2. Revise the plans to show the size and routing of the condensate drain piping.


ELECTRICAL REVIEW COMMENTS
Denied
1. 2018 IBC - 1008.3. Revise the plans to indicate that the emergency lights will have a remote head located on the exterior of the building, at each egress door.


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
Activity Number: TC-COM-0223-00635

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. 2018 IBC - Table 601. Clarification needed on construction type. and/or plans revised. Sheet G003 code data indicates type II-A construction type. Partition type "A" surrounds a primary structural column in the "Sales Area"; however, there is no fire resistance-rated designation as required for type II-A construction primary members. Verify if II-A construction is correct and revise the partition type; or, revise the construction type to be compliant with Table 601.
2. 2018 IBC - 1109.9 & 2009 ANSI A-117.1. Revise the plans to show that 5% of the storage lockers are accessible, and the hardware does not require a pinching or twisting motion.
3. 2018 IBC - 107.2.1. Revise the code data to include whether a fire alarm system is installed.
4. 2018 IBC - 107.2.1. Revise sheet A503 to eliminate the penetration details that are not relevant to this project.


MECHANICAL REVIEW COMMENTS:
Denied
1. 2018 IMC - 307.2.1, 307.2.2. Revise the plans to show the size and routing of the condensate drain piping.


ELECTRICAL REVIEW COMMENTS
Denied
1. 2018 IBC - 1008.3. Revise the plans to indicate that the emergency lights will have a remote head located on the exterior of the building, at each egress door.


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/27/2023 Fire New Construction REVIEW COMPLETED
03/09/2023 PDSD Application Completeness Express REVIEW COMPLETED