Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0223-00608
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/23/2023 | Commercial Electrical | APPROVED | |||
03/20/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/20/2023 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Provide a signature on the seal for all documents. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that the seal shall have both a signature of the registrant and the date the document was sealed. 2. The proposed DOAS unit does not appear to be equipped with an energy recovery module. Explain how the unit is able to have 85.5F (db) air entering the cooling coil at design conditions. Reference: Section 107.2.1, IBC 2018. 3. Show that the new heat pumps will supply at least the same amount of outside air that the previous units supplied. Reference: Section 403.3.1.1, IMC 2018. |
||
02/14/2023 | PDSD Application Completeness | REVIEW COMPLETED |