Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - TC-COM-0223-00606
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/23/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The SR 307 document submitted is incomplete. The previous electrical plan review comment; Please address the electrical plan review comments and provide a written response. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans including a site plan.and detailed scope of work, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. The comment stated to provide complete electrical plans. The notes #1, #2, #3, #4, #5, #6, #7, #8, #9 in the SR – 307 Document were not included. A site electrical plan was not submitted showing the proposed location of the Temporary Electrical Service. And what structure or building was going to utilize the Electricity and its location. The Detailed description that was requested from the original comment was “Please provide a detailed Description. For additional questions contact Dan.SantaCruz@Tucsonaz.gov” The detailed description Did not specify what the Tempoary Service was for and Dan Santa Cruz was not contacted concerning this project. The AIC rating of the electrical service was not specified. The depth of the power pole is not specified or calculations to verify the correct depth. Verify that the service overhead conductors meet the height above grade per NEC 230.24. Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
||
| 05/02/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |