Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0223-00592
Parcel: 127110830

Address:
5901 E 2ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3

Permit Number - TC-COM-0223-00592
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/20/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 The lumen calculations show 19-50W/1150 LUMENS @ EACH FIXTURE. Also, below this shows 19 EXTERIOR LTS @ 21,400 LUMENS EACH. Please clarify.

2 A Special Inspection will be required based on total lumens per acre exceeds 100,000 per acre. Section 106.2.1. Please revise the Special inspection note to reflect this.

Be advised that per COT policy the first part of the sealed Special Inspection Certificate will need to be submitted prior to the plan review approval.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code.
03/11/2024 PDSD Application Completeness Express REVIEW COMPLETED