Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - TC-COM-0223-00592
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/20/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/20/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The lumen calculations show 19-50W/1150 LUMENS @ EACH FIXTURE. Also, below this shows 19 EXTERIOR LTS @ 21,400 LUMENS EACH. Please clarify. 2 A Special Inspection will be required based on total lumens per acre exceeds 100,000 per acre. Section 106.2.1. Please revise the Special inspection note to reflect this. Be advised that per COT policy the first part of the sealed Special Inspection Certificate will need to be submitted prior to the plan review approval. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code. |
||
| 03/11/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |