Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0223-00589
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2023 Commercial Plumbing APPROVED
03/29/2023 Commercial Structural APPROVED
03/06/2023 Site Zoning APPROVED
03/29/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/13/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Provide information to show that a Type B flue is listed for use with a cooking appliance using solid fuel. Reference: Section 502.1 and 503.4, IFGC 2018.
2. Clarify detail 101 with regard to the termination of the chimney above the adjacent parapet. Reference: Section 107.2.1, IBC 2018.
02/13/2023 Fire New Construction REVIEW COMPLETED
02/10/2023 PDSD Application Completeness Express REVIEW COMPLETED