Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0223-00589
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/13/2023 | Commercial Plumbing | APPROVED | |||
03/29/2023 | Commercial Structural | APPROVED | |||
03/06/2023 | Site Zoning | APPROVED | |||
03/29/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/13/2023 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Provide information to show that a Type B flue is listed for use with a cooking appliance using solid fuel. Reference: Section 502.1 and 503.4, IFGC 2018. 2. Clarify detail 101 with regard to the termination of the chimney above the adjacent parapet. Reference: Section 107.2.1, IBC 2018. |
||
02/13/2023 | Fire New Construction | REVIEW COMPLETED | |||
02/10/2023 | PDSD Application Completeness | REVIEW COMPLETED |