Permit Number: TC-COM-0223-00585
Parcel: 110120990

Address:
2650 N WYATT DR

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0223-00585
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/11/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0223-00585


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Refer to drawing C2.0, Provide Section thru 12 feet tall CMU screen wall.
2. Refer to drawing C2.0, Provide Section thru Retaining Wall.
3. Refer to drawing C2.0, Provide Fence info.
4. Refer to Refer to drawing C2.0, It shows the screen wall to be 12 feet high. The Narrative Letter shows the wall height to be 8 feet high. Investigate and make changes as needed.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Denied
A report shall be submitted to the building official identifying the maximum expected quantities of hazardous materials to be stored, used in a closed system and used in an open system, and subdivided to separately address hazardous material classification categories based on Tables 307.1(1) and 307.1(2). The methods of protection from such hazards, including but not limited to control areas, fire protection systems and Group H occupancies shall be indicated in the report and on the construction documents. The opinion and report shall be prepared by a qualified person, firm or corporation approved by the building official and provided without charge to the enforcing agency. (IBC2018,414.1.3).


ELECTRICAL REVIEW COMMENTS
Denied
Electrical permit is denied due to no lighting or power design provided.
Design needs to include at minimum:
A power panel location for lighting and power circuits.
Lighting and power circuit homeruns ie circuit information for the lights and the instrument, alarms, and receptacles.
Exterior lighting calculation to show compliance with Tucson lighting codes.


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1). Narrative states project to include Bulk O2 system for a health facility, is this plan submittal for concrete pad only & is the Bulk O2 system to be submitted under another permit application?? If no, plans need to include everything to do a complete review. NFPA99


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/08/2023 Fire New Construction REQUIRES RESUBMIT -Include on the plans, the amount of liquid oxygen that will be stored/used.
-Include on the plans, the required minimum distance to buildings, lot lines, public streets, public alleys, public ways, or means of egress per the IFC. Include section/table from IFC.
-Include the means of egress/exits for the existing building.

john.vincent@tucsonaz.gov
5203495581
03/09/2023 Site Engineering REQUIRES RESUBMIT See Zoning Comment
03/06/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0123-00585
2650 N Wyatt Dr. – PAD-16
Addition of 22'x28' Concrete Pad for Airgas Capabilities (1st Review)

TRANSMITTAL: March 6, 2023
This site is located in PAD-16, Medical Service is an allowed use in the pad.

1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
02/10/2023 PDSD Application Completeness Express REVIEW COMPLETED