Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0223-00577
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/16/2023 | Commercial Mechanical | APPROVED | |||
05/16/2023 | Commercial Plumbing | APPROVED | |||
05/25/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/25/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Show the location of the electrical breaker panel. If located in a closet or restroom, it must be re-located to a code compliant location NEC 240.24(D), (E). 2 The project is considered commercial. Revise all references to the IRC and replace with 2017 NEC. 3 Is the Breaker panel existing to remain or is it to be replaced? Why does the Panel Schedule call a WP (Water Proof) panel? 4 Provide a luminaire schedule for all the replaced lighting and provide compliance the 2018 IECC. 5 Provide compliance with the 2012 City of Tucson Outdoor Lighting Code for the exterior lighting. 6 Why does the water heater show Circuit #13 as the branch circuit designation? 7 Provide for GFI protected Kitchen Counter top receptacles. NEC 210.8(A). 8 Provide ARC-FAULT protected branch circuits as required per NEC 210.12(A). 9 Verify that there is a GFI protected 120V receptacle on the roof for maintenance of Mechanical Equipment. NEC 210.63. 10 If the breaker panel is being replaced, provide a complete Electrical Line Diagram. Ref 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson Outdoor Lighting Code. |
||
05/03/2023 | PDSD Application Completeness | REVIEW COMPLETED |