Permit Number: TC-COM-0223-00577
Parcel: 13507003E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0223-00577
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2023 Commercial Mechanical APPROVED
05/16/2023 Commercial Plumbing APPROVED
05/25/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/25/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Show the location of the electrical breaker panel. If located in a closet or restroom, it must be re-located to a code compliant location NEC 240.24(D), (E).

2 The project is considered commercial. Revise all references to the IRC and replace with 2017 NEC.

3 Is the Breaker panel existing to remain or is it to be replaced? Why does the Panel Schedule call a WP (Water Proof) panel?

4 Provide a luminaire schedule for all the replaced lighting and provide compliance the 2018 IECC.

5 Provide compliance with the 2012 City of Tucson Outdoor Lighting Code for the exterior lighting.

6 Why does the water heater show Circuit #13 as the branch circuit designation?

7 Provide for GFI protected Kitchen Counter top receptacles. NEC 210.8(A).

8 Provide ARC-FAULT protected branch circuits as required per NEC 210.12(A).

9 Verify that there is a GFI protected 120V receptacle on the roof for maintenance of Mechanical Equipment. NEC 210.63.

10 If the breaker panel is being replaced, provide a complete Electrical Line Diagram.

Ref 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC, 2012 City of Tucson Outdoor Lighting Code.
05/03/2023 PDSD Application Completeness REVIEW COMPLETED