Permit Number: TC-COM-0223-00574
Parcel: 133180360

Address:
6922 E 2ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0223-00574
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2023 Site Engineering NOT REQUIRED
08/18/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/18/2023 Commercial Building REQUIRES RESUBMIT Building Code/Zoning Code Analysis.
With the Zoning Department, ensure that you process the Request for Zoning Authority Clearance & submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. R302.5.1 NOTE: R-4 maximum allowable is 10 clients (Indicate the Occupancy Classification, the number of clients on your drawings as well as indicate that it is a Behavioral Health Facility. Include a statement as part of your code analysis as to how the facility handles any persons receiving custodial care who require limited verbal or physical assistance responding to an emergency situation to complete building evacuation and self preservation. Specify Condition 1 or Condition 2 per IBC 310 (this will determine the type of fire sprinkler system the fire department will require). 1.) On the Site Plan show/indicate the Accessible route from drop off location to the accessible entry door complying to IBC 106 & ANSI A117. In an Emergency, show/locate the gathering area where it is safe from danger per IBC 310.5. 2.) Indicate the clear opening of the doors complying to ANSI A117. 3.) Indicate the clear width of hallways. 4.) Show/locate the side & back grab bars at the Water Closet as well as at the Shower, make sure to indicate the installation of Structural Backer Board for these grab bars per IBC Chapter 11. 5.) Provide Emergency Escape & Rescue Openings per R310 at every bedroom/sleeping space. On the drawing adjacent to the opening(s), indicate the clear opening for both horizontally and vertically and provide the dimension from the finish floor to the bottom of the opening. Indicate if there are obstacles on either side of the opening. 6.) Fire Sprinkler is required per IBC 420 and processed as a separate permit. Submit the drawings to Tucson Fire Department for review and approval. They will conduct fire inspection, the inspection approval document will be required before issuing the Certificate of Occupancy. 7.) A fire alarm is required [IBC 907], If they exist...indicate them on your drawing. If not...please propose to install them. Illumination with emergency backup power is required in all components of the means of egress system [IBC 1008]. Please locate those equipments on your plan (to be inspected by Tucson Fire Department). Electrical work (conductors/wiring/breaker ONLY) related to the installation of Emergency Lights, Lighted Signs, Fire/Audible/Smoke Alarms will be inspected by City of Tucson inspectors, show on your plans so that our inspectors will know what wiring/breaker to inspect and shall also be reviewed as part of this permit. Any new renovation work must be included as part of this building permit. 8.) A Final inspection will be conducted by our inspectors prior to issuance of the Certificate of Occupancy. 9.) An Operator's License must be applied for with the State, the absence of this license shall void this building permit. 10.) Submit a draft copy of the State License application confirming the exact use title for the certificate of occupancy document. 11.) If you have any questions, contact Justin Eder at Justin.Eder@tucsonaz.gov or at 520-837-4976.
07/20/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0223-00574
7525 E. Speedway Bl. – R-1
Behavioral Health Residential for 10 Residents (2nd Review)

TRANSMITTAL: July 20, 2023

This comment was not addressed. Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in R-1 zone (UDC 4.7.8), Behavioral Health Services is an allowed use in the zone (UDC Table 4.8-2), subject to Use Specific Standards 4.9.7.J. 2.a, 3.a, 4.

1. Zoning was not able to find approved permit documents for the “EXIST. GARAGE” (carport enclosed to garage with private suite, “EXIST. CARPORT” in the front yard and rear yard or the “EXIST. OFFICE”. Either provide approved permit documents or theses structures will need to be permitted prior to approval of this plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/27/2023 Fire New Construction REVIEW COMPLETED
07/14/2023 PDSD Application Completeness Express REVIEW COMPLETED