Permit Number: TC-COM-0223-00569
Parcel: 13017149A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0223-00569
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
03/16/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: TC-COM-0223-00569

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
APPROVED - SUBJECT TO THE FIELD INSPECTOR'S APPROVAL OF THE EXISTING EQUIPMENT AND STRUCTURE


BUILDING REVIEW COMMENTS:
Denied
Still need the COMcheck report showing compliance of the interior and exterior lighting - mandatory section C405.
Still need to show the new or existing exterior exit discharge lighting connected to the emergency lighting as required by Section 1008.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
APPROVED - SUBJECT TO THE FIELD INSPECTOR'S APPROVAL OF THE EXISTING EQUIPMENT AND STRUCTURE


ELECTRICAL REVIEW COMMENTS
Denied
Still need the COMcheck report showing compliance of the interior and exterior lighting - mandatory section C405.
Still need to show the new or existing exterior exit discharge lighting connected to the emergency lighting as required by Section 1008.


PLUMBING REVIEW COMMENTS:
Conditionally Approved
APPROVED - SUBJECT TO THE FIELD INSPECTOR'S APPROVAL OF THE EXISTING EQUIPMENT AND STRUCTURE


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/10/2023 PDSD Application Completeness REVIEW COMPLETED