Permit Number: TC-COM-0126-00143
Parcel: 11706168A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0126-00143
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2026 Commercial Electrical Standard APPROVED
02/24/2026 Commercial Plumbing Standard APPROVED
02/27/2026 Site Zoning Standard APPROVED
02/24/2026 Water - PDSD Standard APPROVED
02/06/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
02/25/2026 Site Engineering Standard NOT REQUIRED
03/02/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/27/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please amend the Project Data under the A2 occupancy classification to indicate occupancy use. For example,
A. Banquet halls
B. Casinos (gaming areas)
C. Nightclubs
D. Restaurants, cafeterias and similar dining facilities (including associated commercial kitchens)
E. Taverns and bars
2. Please amend the plans to provide a detailed description of the work involved in this permit’s scope. IBC 105.3 as there might be an expanded scope after addressing these comments.
3. IBC Section 1006.2.1 requires two exits from this proposed tenant space based on the occupant load (49) and the travel distance (75 feet), as indicated in IBC Table 1006.2.1, Spaces with One Exit or Exit Access Doorway. Please revise the plans to provide two exits. The exits must be separated by a distance equal to not less than one-third of the maximum diagonal dimension of space, in accordance with IBC Section 1007.1.1. Based on a diagonal measurement of 86 feet 7 inches, the required minimum separation is one-third of that dimension, which is approximately 28 feet 10 inches (just under 29 feet).
4. Spaces intended for assembly use are required to be designed for a minimum floor live load of 100 psf. The structural calculations from the previous permit appear to indicate a design live load of only 40 psf. International Building Code Table 1607.1 requires a minimum live load of 100 psf for assembly areas, which is non-reducible. Please have an Arizona-licensed structural engineer evaluate the existing structure and provide stamped and sealed structural design, construction drawings, and supporting calculations demonstrating compliance with the required design live load, in accordance with I B C Table 1607.1.
02/24/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0126-00143
ADDRESS/PARCEL: 314 E CONGRESS ST TUCSON, AZ 85701

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. The occupant load for this space has increased from 23 occupants (from permit # T22CM03260) to 156 occupants. Please provide mechanical ventilation calculations demonstrating that the existing ventilation system is capable of supplying the minimum required outdoor air for this space. Reference: Section 403.3.1.1, IMC 2024.
2. The previously approved plans under permit T22CM03260 show two ovens and a sink within the breakroom. These fixtures are not shown on the current floor plan. Please clarify whether these items are being removed as part of this scope of work. If the breakroom is to remain, revise the occupant load calculations as necessary to account for this space. Reference: Section 107.2.1, IBC 2024.
03/02/2026 Fire New Construction Standard REQUIRES RESUBMIT 1. Resolve all building comments.
2. Include the total occupant load for the entire building.
3. Include the fire alarm information on the code analysis. Does it have an existing fire alarm? Is it a voice alarm? Will you be modifying the existing fire alarm?
john.vincent@tucsonaz.gov
5203495581
02/03/2026 PDSD Application Completeness Express REVIEW COMPLETED