Permit Number: TC-COM-0126-00143
Parcel: 11706168A

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0126-00143
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2026 Commercial Electrical Standard APPROVED
02/24/2026 Commercial Plumbing Standard APPROVED
02/24/2026 Water - PDSD Standard APPROVED
02/06/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
N/A Site Engineering Standard PENDING ASSIGNMENT
N/A Site Zoning Standard PENDING ASSIGNMENT
02/24/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0126-00143
ADDRESS/PARCEL: 314 E CONGRESS ST TUCSON, AZ 85701

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. The occupant load for this space has increased from 23 occupants (from permit # T22CM03260) to 156 occupants. Please provide mechanical ventilation calculations demonstrating that the existing ventilation system is capable of supplying the minimum required outdoor air for this space. Reference: Section 403.3.1.1, IMC 2024.
2. The previously approved plans under permit T22CM03260 show two ovens and a sink within the breakroom. These fixtures are not shown on the current floor plan. Please clarify whether these items are being removed as part of this scope of work. If the breakroom is to remain, revise the occupant load calculations as necessary to account for this space. Reference: Section 107.2.1, IBC 2024.
02/03/2026 PDSD Application Completeness Express REVIEW COMPLETED