Permit Number: TC-COM-0126-00137
Parcel: 10512024F

Address:
4040 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0126-00137
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/20/2026 Commercial Building Standard APPROVED
02/05/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
02/23/2026 Site Engineering Standard NOT REQUIRED
02/24/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/12/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0126-00137 (4040 N ORACLE RD TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The removal and re-installation of the PV panels requires compliance with the currently adopted codes. This includes the installation of rapid shutdown. Provide rapid shutdown labels and placard on the building, NEC 690.56(C) & 705.10.
2. Provide updated electrical plans, sealed by an Arizona Registered Electrical Engineer, showing the re-installation of the PV panels and inclusion of the rapid shutdown devices, initiation device and updated signage. NEC 690.12(C).
02/24/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0126-00137
4040 N. Oracle Rd. Tucson, AZ 85705
Temporary Removal and Installation of Solar System on Roof (1st Review)

TRANSMITTAL DATE: 2/24/2026

This site is located in the C-2 zone (UDC 4.7.21). General Merchandise Sales – Large Retail Establishment is an allowed use subject to Use Specific Standards 4.9.9.D.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: As a new 20’x20’ electric utility easement is being proposed in the parking lot, please include the recordation information for this new easement.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
02/20/2026 Fire New Construction Standard REVIEW COMPLETED
02/02/2026 PDSD Application Completeness Express REVIEW COMPLETED