Permit Number: TC-COM-0126-00129
Parcel: 117067410

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0126-00129
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2026 Commercial Electrical Standard APPROVED
02/09/2026 Outdoor Lighting Standard APPROVED
02/19/2026 Water - PDSD Standard APPROVED
02/19/2026 Commercial Mechanical Standard NOT REQUIRED no mechanical work being done
02/23/2026 Site Engineering Standard NOT REQUIRED
03/02/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/27/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please amend the plans to demonstrate that not less than 5% of each type of seating and standing spaces are accessible/ IBC 1110.14
2. IEBC 306.7 requires that accessibility be provided to the altered spaces. Where the existing path of travel elements, which entails a primary entrance, a primary path of travel, sanitary facilities serving the area, a drinking fountain, and signs. If these items are in full compliance with the current code, provide a statement indicating this on the cover sheet of the drawings. Otherwise, accessibility upgrades shall be required in accordance with IEBC.305.7. 1. If the cost of providing or upgrading the items above to be accessible is disproportionate to the cost of construction (exceeds 20% of the cost of construction not including accessibility upgrades), please provide information to verify construction costs.
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
02/19/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0126-00129
ADDRESS/PARCEL: 345 E CONGRESS ST Unit:UNIT 101 TUCSON, AZ 85705

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Floor sinks located within the kitchen area shall discharge through a grease interceptor. Note 3 on Sheet P201 states sinks are to be routed to a grease trap and then routed to the floor sink. Reference: Section 1003.3, IPC 2024, as amended by the City of Tucson.
2. Verify if an existing grease interceptor is currently in place to prevent the discharge of fats, oil, and grease into the public sewer. Reference: Section 1003.1, IPC 2024.
3. Please provide an equipment schedule identifying new and existing equipment. The schedule shall coordinate with the equipment item numbers referenced in the sheet notes on the plumbing drawings. Reference: Section 107.2.1, IBC 2024.
02/11/2026 Design Review Standard REQUIRES RESUBMIT This property is located within the boundaries of the Rio Nuevo Area (RNA) overlay zone. A Design Package will need to be submitted as a subrecord of TC-COM-0126-00129, demostrating compliance with applicable requirements specified in Unified Development Code (UDC) Section 5.12.7 (https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-23005). Please note historic preservation review will not be required. The Design Package will need to submitted with the materials included in the Special Dictricts Application Instructions (https://www.tucsonaz.gov/files/sharedassets/public/v/3/pdsd/documents/submission-documents/special_districts_application_instructions_7.18.23.pdf). The Design Package will need to be reviewed by the Design Review Board (DRB). Here's an overview of the RNA review process: https://www.tucsonaz.gov/files/sharedassets/public/v/3/pdsd/documents/planning-amp-zoning/rna-application-and-review-process.pdf. If you have any questions, pelase let me know: maria.gayosso@tucsonaz.gov. Thank you.
02/24/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
PDSD Zoning Review Section

PROJECT:
TC-COM-0126-00129
345 E. Congress St. Unit 101 Tucson, AZ 85705
Block A Bar TI (1st Review)

TRANSMITTAL DATE: 2/24/2026

Comment: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

This site is located in the OCR-2 zone (UDC 4.7.27).

1. Comment: As this site is located within the COT Rio Nuevo Area (RNA), RNA review must be completed and approved prior to zoning approval of this building permit. Please contact Maria Gayosso at Maria.Gayosso@tucsonaz.gov if you have questions about the RNA review process. Site Zoning cannot approve this permit until the RNA review has been approved. Additional information about RNA requirements can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/3/pdsd/documents/planning-amp-zoning/rna-application-and-review-process.pdf.
2. Comment: Additional comments may be forthcoming based on responses to zoning comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
03/02/2026 Fire New Construction Standard REVIEW COMPLETED
02/02/2026 PDSD Application Completeness Express REVIEW COMPLETED