Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0126-00121
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/06/2026 | Commercial Building | APPROVED | |||
| 02/09/2026 | Water - PDSD | APPROVED | |||
| 02/09/2026 | Commercial Mechanical | NOT REQUIRED | |||
| 02/09/2026 | Commercial Plumbing | NOT REQUIRED | |||
| 02/04/2026 | Site Engineering | NOT REQUIRED | |||
| 02/11/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/29/2026 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0126-00121 (2740 N CAMPBELL AV TUCSON, AZ 85719) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Provide a panel schedule, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1. 2. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1. Each electrical outlet should be labeled by panel and circuit number. |
||
| 02/11/2026 | Site Zoning | REQUIRES RESUBMIT | 1. COMMENT: The proposed use of the suite is Fast Auto Loans, a title loan company. This use is classified within the Unified Development Code as a "Commercial Services Land Use Group - Financial Institution, Non-chartered Institution". Provide a general note on the cover sheet indicating this as the use. 2. COMMENT: Per UDC Table 4.8-4, this use is not permitted in the C-1 zone. No special exception procedure is available to allow the use. Contact Fernando Garcia, Lead Planner, Site Zoning at fernando.garcia2@tucsonaz.gov. |
||
| 02/11/2026 | Fire New Construction | REVIEW COMPLETED | |||
| 01/29/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |