Permit Number: TC-COM-0126-00120
Parcel: 11917013H

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0126-00120
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2026 Commercial Building APPROVED
02/09/2026 Commercial Mechanical APPROVED
02/09/2026 Water - PDSD APPROVED
02/09/2026 Commercial Plumbing NOT REQUIRED
02/03/2026 Site Engineering NOT REQUIRED
02/11/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/29/2026 Addressing Validation REQUIRES RESUBMIT If you have questions please contact me at Drew.Szentesy@tucsonaz.gov or contact the Building Official at Building_Official@tucsonaz.gov

The address on the permit location does not match the address on the uploaded documents. The unit number 110 is not included on the construction plans. Please either correct the address on the uploaded documents and resubmit or submit a change of address request in the permit sub-records.
01/29/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0126-00120 (3504 S 6TH AV Unit:UNIT 110 TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide a panel schedule, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1.
2. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1. Each electrical outlet should be labeled by panel and circuit number.
02/11/2026 Site Zoning REQUIRES RESUBMIT 1. COMMENT: The proposed use of the suite is Fast Auto Loans, a title loan company. This use is classified within the Unified Development Code as a "Commercial Services Land Use Group - Financial Institution, Non-chartered Institution". Provide a general note on the cover sheet indicating this as the use.

2. COMMENT: Per UDC Table 4.8-4, this use is only permitted in the C-2 zone with a Zoning Examiner Special Exception Land Use Procedure (SELUP).

The existing neighboring site, at 3460 S 6th Av, is also within C-2, but is considered a legal nonconforming use that was established prior to new code and ordinances prohibiting non-charted financial institutions from operating in C-2 zoning without a SELUP.

If the applicant desires to continue with this permit, an approved SELUP will be required before Site Zoning can provide final approval for this permit. Contact the Entitlements Section at rezoning@tucsonaz.gov for more information and to reach out the Entitlements Team.

Contact Fernando Garcia, Lead Planner, Site Zoning at fernando.garcia2@tucsonaz.gov.
02/11/2026 Fire New Construction REVIEW COMPLETED
01/29/2026 PDSD Application Completeness Express REVIEW COMPLETED