Permit Number: TC-COM-0126-00103
Parcel: 121111910

Address:
4826 E PIMA ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0126-00103
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/19/2026 Site Zoning Standard APPROVED
02/11/2026 Water - PDSD Standard APPROVED
02/02/2026 Commercial Electrical Standard NOT REQUIRED no electrical work
01/30/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
02/18/2026 Site Engineering Standard NOT REQUIRED
02/19/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/17/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please amend plans to show the locations of mirrors in the new restroom and demonstrate how the configuration meets the privacy requirements of IBC 1210.3
2. Please amend the plans to provide walls or partitions and a door enclosing at least one of the water closets to ensure privacy. Per Exception #2 Toilet rooms located in child day care facilities and containing two or more water closets shall be permitted to have one water closet without an enclosing compartment. IBC 1210.3.1
3. Please amend the plans to specify the materials to be used on the walls and partitions within 2 feet of service sinks, and water closets to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. IBC 1210.2.2
4. Please amend the plans to specify the floor finish and base that extends 4” up the surrounding walls. IBC 1210.2.1
5. Please amend the plans to provide interior elevations to all 4 walls of the restroom to demonstrate compliance with comments 1-4 above. Additionally, provide dimensions showing the height and location of all plumbing fixtures and accessories meeting the accessibility requirements for a children’s restroom. IBC 107.2.1 & 2017 ICC A117.1
6. Please show the following children’s accessibility information on the plans. IBC 107.2.1
A. Show the clear turning space, and clear floor space for each fixture. Additionally show the approach as forward or parallel where applicable. IBC 107.2.1 2017 ICC A117.1 604.9.5, 604.9.5.2
B. Please show the dimensioned positioning requirements for Children’s Lavatory 2017 ICC A117.1. 606.2
C. Please show the dimensioned positioning requirements for Toilet compartment. 604.1, 2017 ICC A117.1 604.9.2.2, 604.9.5, 604.11,
609.4.2
D. Please show the dimensioned positioning requirements for Water closet. 2017 ICC A117.1 604.11.2, 604.11.4
E. Please show the dimensioned positioning requirements for Toilet paper dispensers. 2017 ICC A117.1 604.11.7
F. Please show the dimensioned positioning requirements grab bar positions. 2017 ICC A117.1 609.4.2
7. Show the clear turning space, and clear floor space for each fixture. Additionally show the approach as forward or parallel where applicable. IBC 107.2.1 2017 ICC A117.1 604.9.5, 604.9.5.2

Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
02/11/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0126-00103
ADDRESS/PARCEL: 4826 E PIMA ST TUCSON, AZ 85712

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Please show the existing exhaust fan, show the flow rate (cfm), and provide information on the sequence of operation for the restroom exhaust fan to show that all of the air supplied to the restroom will be exhausted. Reference: Section 403.2.1 (4), IMC 2024.
02/11/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0126-00103
ADDRESS/PARCEL: 4826 E PIMA ST TUCSON, AZ 85712

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Provide a water riser diagram and clarify how the hot water recirculation will work with the 3 lavatories. Reference: Section 107.2.1, IBC 2024.
02/18/2026 Fire New Construction Standard REVIEW COMPLETED
01/27/2026 PDSD Application Completeness Express REVIEW COMPLETED