Permit Number: TC-COM-0126-00099
Parcel: 11707226B

Address:
747 S 6TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0126-00099
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2026 Commercial Electrical APPROVED
02/05/2026 Commercial Plumbing APPROVED
02/06/2026 Site Zoning APPROVED
02/04/2026 Water - PDSD APPROVED
02/03/2026 Site Engineering NOT REQUIRED
02/06/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/27/2026 Addressing Validation REQUIRES RESUBMIT If you have questions please contact me at Drew.Szentesy@tucsonaz.gov or contact the Building Official at Building_Official@tucsonaz.gov

The address has unit numbers attached to it in our system. Please submit a change of address request through sub records to add the unit number to the permit location to match the site plans. This permit appears to be for Unit 101. For help navigating sub records: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf
02/06/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please amend the restroom plan to show a clear floor space of 60 inches measured perpendicularly from the sidewall. 2017 ICC A117.1 604.3 The lavatory cabinet appears to encroach into water closet clear floor space. Items that cannot overlap the clear floor space for the water closet include counters or the accessible lavatory. 2017 ICC A117.1 604.3.3
2. Please amend the plans to provide an interior elevation or otherwise indicate the breakroom counter height (34 maximum height) 2017 ICC A117.1 902.4
A. Include the sink height to show or note the front of lavatories and sinks shall be 34 inches maximum above the floor, measured to the higher of the rim or counter surface. 2017 ICC A117.1 606.3 Please show the clear floor space to indicate either a front approach or a parallel approach. 2017 ICC A117.1 606.2
3. Please amend the plans to indicate a parallel or forward approach at the receptionist’s counter. 2017 ICC A117.1 904.3.2 Parallel approach 904.3.3 Forward approach
4. Please amend the plans to clearly identify the occupant load factors and resulting occupant loads for each room and space. IBC Section 1004.5. For example, the break room and waiting area should be calculated at 15 square feet net per person, while the remaining areas may be calculated at 150 square feet gross per person.
This revision is not expected to significantly affect the total occupant load; however, it will provide a more accurate and code-compliant Occupant Load Calculation Table under the Code Review.
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
02/05/2026 Commercial Mechanical REQUIRES RESUBMIT If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
Footnote b on Table 403.3.1.1, IMC 2024 states that mechanical exhaust is required for the beauty salon and no air from the beauty salon may be recirculated to any other space. Fan coils FC-1 and FC-2 appear to be recirculating air from the beauty salon to the waiting area, reception, restroom, staff area, and the hallway. Reference: Section 403.2.1 (3), IMC 2024.
02/05/2026 Fire New Construction REVIEW COMPLETED
01/27/2026 PDSD Application Completeness Express REVIEW COMPLETED