Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0126-00085
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/26/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/22/2026 | Commercial Electrical Express | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0126-00085 (2520 N 15TH AV TUCSON, AZ 85705) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC). Electrical Review: Plans shall include (as necessary for scope of work), but may not be limited to items below: 1. The addition of the 2 new walk-in refrigerators and 2 new HVAC units, requires complete electrical plans for this work. 2. Provide an electrical demo plan for any demo’ed electrical or appliances. 3. Provide an electrical plan that shows the location of the panel, circuits, underground or overhead routes, receptacles, or other modified or new electrical work. 4. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4. 5. Show a GFCI (NEC 210.8(B)(4)) receptacle outlet on the same level within 25’ of exterior HVAC equipment, NEC 210.63. 6. Provide a panel schedule, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1. 7. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1. Each electrical outlet should be labeled by panel and circuit number. NOTE: Depending on the full scope of work, this could require a Tenent Improvement permit. Additional comments may be forthcoming with complete electrical plans for the building and site. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 01/26/2026 | Commercial Mechanical Express | REQUIRES RESUBMIT | If the installation of two additional A/C units and two new walk-in refrigerators will be included in this activity, provide construction documents drawn to scale and with sufficient detail and clarity to demonstrate that the work complies with the applicable codes. The mechanical design and calculations shall be performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Reference: Sections 107.1 and 107.2.1, IBC 2024. | ||
| 01/22/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |