Permit Number: TC-COM-0126-00058
Parcel: 14101013E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0126-00058
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2026 Commercial Electrical Standard APPROVED
02/03/2026 Site Engineering Standard APPROVED
02/04/2026 Commercial Plumbing Standard NOT REQUIRED
01/27/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
02/04/2026 Water - PDSD Standard NOT REQUIRED
02/06/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/16/2026 Addressing Validation REQUIRES RESUBMIT If you have questions regarding the addressing validation, please contact Drew Szentesy at Drew.Szentesy@tucsonaz.gov or the Tucson Building Official at Building_Offical@tucsonaz.gov

The address on the permit location is not included on the construction plans. Please add the address to the construction plans and resubmit after other reviews are complete.
02/05/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please provide one accessible toilet room with an accessible route connecting the accessible parking, the sales office and the accessible toilet room is to be provided as part of the Model Home Complex. IBC 1109 & IBC 1104

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
02/04/2026 Commercial Mechanical Standard REQUIRES RESUBMIT If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
1. Clarify the location of the air handler. Provide maintenance access. Reference: Section 306.3, IMC 2024.
2. Show how the proposed ducts will penetrate the fire-resistance-rated partitions. Reference: Sections 603.7 and 607.1, IMC 2024.
3. Show the size, routing, and termination of the condensate drain. Reference: Section 307.2.1, IMC 2024 as amended by the City of Tucson.
4. Secure the refrigerant circuit access ports of the condensing units to prevent unauthorized access. Reference: Section 1101.9, IMC 2024.
02/06/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0126-00058
7428 S. Pyramid Ridge Dr. Tucson, AZ 85747
Convert Garage to Sales Office (1st Review)

TRANSMITTAL DATE: 2/6/2026

The site is located in PAD-38 (Escalera PAD).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: A separate Temporary Use Permit (TUP) will be required prior to approval of this building permit. If you have questions about the TUP, please contact Mark Castro at Mark.Castro@tucsonaz.gov.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
02/05/2026 Fire New Construction Standard REVIEW COMPLETED
01/16/2026 PDSD Application Completeness Express REVIEW COMPLETED