Permit Number: TC-COM-0126-00055
Parcel: 10509546C

Address:
68 W RIVER RD

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0126-00055
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2026 Commercial Electrical Standard APPROVED
02/03/2026 Commercial Plumbing Standard APPROVED
02/03/2026 Water - PDSD Standard APPROVED
01/22/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
01/16/2026 Site Engineering Standard NOT REQUIRED
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
N/A Site Zoning Standard PENDING ASSIGNMENT
02/03/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0126-00055
ADDRESS/PARCEL: 68 W RIVER RD TUCSON, AZ 85704

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Hood canopies shall extend at least 6” horizontally on all open sides beyond the edge of the top horizontal surface of the appliances (i.e. the pizza ovens) under the hood. Reference: Section 507.1.6.1, IMC 2024.
2. Revise detail A1/M501 to show how the new Type I hood is supported from the building structure. Reference: Sections 302.1 and 507.2.4, IMC 2024.
3. The mechanical plan, M102, shows two high velocity diffusers located in close proximity to the ends of the Type I hood. Verify that the location and type of air outlets complies with the hood manufacturer’s installation instructions and does not reduce the effectiveness of the exhaust system. Reference: Sections 304.1 and 508.1, IMC 2024.