Permit Number: TC-COM-0126-00051
Parcel: 106050890

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0126-00051
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2026 Commercial Mechanical Standard APPROVED
04/02/2026 Commercial Plumbing Standard APPROVED
04/07/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/02/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0126-00051
ADDRESS/PARCEL: (570 W PRINCE RD Unit: UNIT 1 TUCSON, AZ 85705)

Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. LETTER FROM ARCHITECT
a. Item #2, patio beam
i. Please ensure the replacement is included within the Engineer’s suggested recommendations within his/her fire damage assessment/report.
b. Item #2, some windows will be replaced
i. On the plan, please identify which window to remain existing and which windows are to be replaced
c. Item #2, electrical
i. Please locate/label the smoke detectors and carbon monoxide detector.
d. Item #8, no gas
i. Please add a note on the drawing indicating, no gas used in unit #1.
e. Item #9, Engineer’s reports.
i. The Engineer’s reports were not submitted.
ii. Please submit the engineer’s fire damage assessment.
1. Please ensure to include the engineer’s recommendations as to solutions to the damages such as the replacement structural member sizes along with their structural calculation as he/she desire to include. This includes wall studs and framing and roof/floor joists.
2. Please ensure that the report is sealed/signed/dated by the Structural Engineer.
2. FIRE PARTITION
a. Provide drawings illustrating the condition within the dwelling unit complying to the below code regulation.
b. Fire partitions shall have a fire-resistance rating of not less than 1 hour per IBC 708.3
c. IBC 708.4 Continuity. Fire partitions shall extend from the top of the foundation or floor/ceiling assembly below and be securely attached to one of the following:
i. The underside of the floor or roof sheathing, deck or slab above.
ii. The underside of a floor/ceiling or roof/ceiling assembly having a fire-resistance rating that is not less than the fire-resistance rating of the fire partition.
3. Please resubmit.
04/07/2026 Fire New Construction Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
03/16/2026 PDSD Application Completeness Express REVIEW COMPLETED