Permit Number: TC-COM-0126-00021
Parcel: 115190350

Address:
1425 W GRANT RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0126-00021
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2026 Commercial Building Standard APPROVED
01/16/2026 Commercial Electrical Standard APPROVED
01/29/2026 Commercial Plumbing Standard APPROVED
01/26/2026 Site Zoning Standard APPROVED
01/29/2026 Water - PDSD Standard APPROVED
01/27/2026 Landfill Standard NOT REQUIRED Property outside the 500 ft. buffer subject to landfill ordinance.
01/15/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
01/13/2026 Site Engineering Standard NOT REQUIRED
01/29/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/29/2026 Commercial Mechanical Standard REQUIRES RESUBMIT If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
1. Hood canopies shall extend at least 6” horizontally on all open sides beyond the edge of the top horizontal surface of the appliances (i.e. the pizza ovens)under the hood. Reference: Section 507.1.6.1, IMC 2024.
2. Revise detail A1/M501 to show how the new Type I hood is supported from the building structure. Reference: Sections 302.1 and 507.2.4, IMC 2024.
3. The mechanical plan, M102, shows two high velocity diffusers located in close proximity to the ends of the Type I hood. Verify that the location and type of air outlets complies with the hood manufacturer’s installation instructions and does not reduce the effectiveness of the exhaust system. Reference: Sections 304.1 and 508.1, IMC 2024.
01/28/2026 Fire New Construction Standard REVIEW COMPLETED
01/07/2026 PDSD Application Completeness Express REVIEW COMPLETED