Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0126-00020
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/26/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/26/2026 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | The air balance report shows that exhaust fan EF-1, serving the restrooms, is providing only 63% of the design air flowrate. Reference: Section 608.1, IMC 2024, as amended by the City of Tucson. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 05/26/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |